考虑中性线影响的低压配电网监测
Monitoring of Low Voltage Distribution Grid Considering the Neutral Conductor
摘要:
三相加权最小二乘(WLS)状态估计(SE)是低压配电网(LVDG)最常用的监测方法,它最初是为中压配电网(MVDG)开发的。这种方法隐含地应用于LVDG,假设中性线代表整个系统的零电位。然而,由于用户负载高度不对称,中性线通常仅在中低压Transformer变电站接地,因此这种假设通常对LVDG无效。因此,如果将此方法应用于LVDG的监测,可能会降低WLS SE的性能,导致结果不准确。在本文中,初步进行调查,以评估传统的WLS SE方法的性能时,应用于LVDG的监测。这项研究的结果表明,这种方法的性能是不一致的,是高度受LVDG的操作条件。鉴于这些结果,提出并开发了一种新的方法,该方法考虑了中性导体的影响,因此与传统方法相比,实现了出色的性能。
英文摘要:
The most widely used method for monitoring Low Voltage Distribution Grids (LVDGs) is the three phase Weighted Least Squares (WLS) State Estimation (SE), which was initially developed for Medium Voltage Distribution Grids (MVDGs). This methodology is implicitly applied in LVDGs with an assumption that the neutral conductor represents a zero potential across the whole system. However, this assumption is often not valid for LVDGs as the consumers loads are highly asymmetrical and the neutral conductor is usually grounded only at the MV-LV transformer substation. Therefore, if this method is applied for the monitoring of LVDGs it may deteriorate the performance of the WLS SE leading to inaccurate results. In this paper, an investigation is initially conducted in order to evaluate the performance of the conventional WLS SE methodology when applied for the monitoring of LVDGs. The results of this study indicate that the performance of this methodology is not consistent and is highly affected by the operating conditions of the LVDG. In view of these results, a new methodology is proposed and developed that takes into consideration the effect of the neutral conductor and as a result an outstanding performance is achieved compared to the conventional methodology.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。