校正控制:结合频率控制和拥塞管理的统一控制器的稳定性分析
Corrective control: stability analysis of Unified Controller combining frequency control and congestion management
摘要:
本文分析了统一控制器(UC)的稳定性,它结合了频率控制和阻塞管理,从而使人们有可能从预防性电力系统控制的纠正。UC作者的早期工作证明了该方法的渐近稳定性,但证明是基于涡轮机和涡轮机调速器的简化一阶模型。我们表明,高阶模型的水轮机调速器导致本征值小,但积极的实部。因此,我们开发了一种修改的方法,使物理和控制系统,因此在所有的特征值具有负的实部的结果。我们说明了一个现实的新英格兰电力系统的39节点模型在电力系统仿真(PST)中实现的模型的修改的有效性。
英文摘要:
This paper analyses stability of the Unified Controller (UC) that combines frequency control and congestion management and therefore makes it possible to move from preventive to corrective power system control. Earlier work by the authors of UC proved asymptotic stability of the methodology but the proof was based on a simplified first-order model of the turbine and turbine governor. We show that a higher order model of the turbine governor leads to eigenvalues with small but positive real parts. Consequently, we develop a modification of the methodology that decouples the physical and control systems and therefore results in all the eigenvalues having negative real parts. We illustrate the effectiveness of the modification on a realistic model of 39-bus model of New England power system implemented in Power System Toolbox (PST).
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。