EAST ECRH系统中回旋管的过流保护

Overcurrent Protection for Gyrotrons in EAST ECRH System

Weiye Xu, Handong Xu, Jianqiang Feng, Yong Yang, Huaichuan Hu, Fukun Liu, Yunying Tang

摘要:

本文针对EAST电子回旋共振加热系统中回旋管的安全问题,设计了一种过流保护系统。建立了两个过流保护系统,一个快速的,一个缓慢的。快速型采用电流互感器作为电流传感器。建立了电流互感器和超导磁体的数学模型,采用FI法分析了环境磁场对电流互感器的影响。分析结果表明,电流互感器附近位置的磁感应强度必须小于0. 002 T,即,电流互感器应放置在距磁铁中心大于2.2米的位置,以保证其正常工作。慢的一个使用分流器来监控电流。快速保护电路和慢速保护电路分别采用反熔丝FPGA和定时器实现信号处理。快速保护电路的响应时间小于100 ns,慢速保护电路的响应时间小于31 μs。

英文摘要:

In this paper, an overcurrent protection system is designed to ensure the safety of the gyrotrons in the EAST ECRH system. Two overcurrent protection systems were established, a fast one and a slow one. The fast one uses the current transformers as the current sensors. The models of the current transformers and the superconducting magnet were built to analyze the effect of the environmental magnetic field on the current transformers using FI method. The analysis results show that the magnetic induction at the position near the current transformers must less than 0.002 T, i.e., the current transformers should be placed at a distance greater than 2.2 meters from the magnet center to ensure its normal work. The slow one uses the shunt to monitor the currents. An anti-fuse FPGA and a timer is used to realize the signal processing in the fast protection circuit and the slow protection circuit respectively. The response time of the fast protection circuit is less than 100 ns, and the response time of the slow protection circuit is less than 31 μs.