FLiER:利用稀疏PMUs进行实用拓扑更新检测
FLiER: Practical Topology Update Detection Using Sparse PMUs
AI总结:
FLiER通过稀疏PMUs数据检测电力网络拓扑变化,采用局部线性化和新滤波方法提高效率,实验验证于IEEE 57/118节点及波兰冬季峰值网络。
摘要:
本文提出了一种指纹线性估计程序(FLiER),利用稀疏部署的相量测量单元(PMUs)数据来检测电力网络中的拓扑变化。当网络中的一条线路、负载或发电机发生故障,或者当变电站重新配置时,事件会留下独特的
英文摘要:
In this paper, we present a Fingerprint Linear Estimation Routine (FLiER) to identify topology changes in power networks using readings from sparsely-deployed phasor measurement units (PMUs). When a power line, load, or generator trips in a network, or when a substation is reconfigured, the event leaves a unique "voltage fingerprint" of bus voltage changes that we can identify using only the portion of the network directly observed by the PMUs. The naive brute-force approach to identify a failed line from such voltage fingerprints, though simple and accurate, is slow. We derive an approximate algorithm based on a local linearization and a novel filtering approach that is faster and only slightly less accurate. We present experimental results using the IEEE 57-bus, IEEE 118-bus, and Polish 1999-2000 winter peak networks.