电压崩溃与功率流的ODE方法--一条静态消/产失序馈线的分析
Voltage Collapse and ODE Approach to Power Flows: Analysis of a Feeder Line with Static Disorder in Consumption/Production
摘要:
我们考虑一个模型的配电馈线连接多个负载的子站。电压直接控制在线路的头部(变电站),然而,电压在线路的任何地方都受到波动的影响,这是由实际和无功分布式功耗/发电的不规则性引起的。缺乏对沿线电压的直接控制可能导致电压不稳定,也称为电压崩溃-电力工程文献中众所周知并有记载的现象。新兴的光伏技术,这带来了新的可再生能源发电的来源,但也有助于显着增加潮流波动的动机,我们重新审视电压稳定和崩溃的现象。在用户数量较大且潮流空间变化是沿馈线位置的光滑函数的情况下,推导了一组潮流常微分方程,验证了电压崩溃现象,并通过模拟随机常微分方程研究了注入和消耗的无序和不规则性对电压分布的影响。我们观察到,无序导致非线性放大的电压变化在年底的线电压崩溃点接近。我们还发现,当在与线的长度相比足够小的尺度上相关时,该无序自平均,即电压分布对于无序的任何单独实现保持空间平滑,并且仅在与线的长度相当的尺度上相关。最后,我们解释了为什么在一个天真的一个发电机一个负载模型中不能描述的综合效果的混乱的电压在线路末端。
英文摘要:
We consider a model of a distribution feeder connecting multiple loads to the sub-station. Voltage is controlled directly at the head of the line (sub-station), however, voltage anywhere further down the line is subject to fluctuations, caused by irregularities of real and reactive distributed power consumption/generation. The lack of a direct control of voltage along the line may result in the voltage instability, also called voltage collapse - phenomenon well known and documented in the power engineering literature. Motivated by emerging photo-voltaic technology, which brings a new source of renewable generation but also contributes significant increase in power flow fluctuations, we reexamine the phenomenon of voltage stability and collapse. In the limit where the number of consumers is large and spatial variations in power flows are smooth functions of position along the feeder, we derive a set of the power flow Ordinary Differential Equations (ODE), verify phenomenon of voltage collapse, and study the effect of disorder and irregularity in injection and consumption on the voltage profile by simulating the stochastic ODE. We observe that disorder leads to nonlinear amplification of the voltage variations at the end of the line as the point of voltage collapse is approached. We also find that the disorder, when correlated on a scale sufficiently small compared to the length of the line, self-averages, i.e. the voltage profile remains spatially smooth for any individual realization of the disorder and is correlated only at scales comparable to the length of the line. Finally, we explain why the integrated effect of disorder on the voltage at the end of the line cannot be described within a naive one-generator-one-load model.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。